Mag Lock or Electric Strike for a Server Room Door in Ontario?

Mag lock or electric strike on a server room door in Ontario? Which fits, what the 2024 Building Code requires, permits, schools and fire-rated doors.

Illustration: steel double door into a data hall with a card reader beside it and a dome camera above

Key points

  • For most Ontario server rooms, an electric strike or electrified lock fits better than a mag lock: people leave by the lever, and fail-secure models stay locked.
  • A mag lock needs a code-compliant fire alarm system and must release on alarm, power loss, wiring fault, a staff switch and a pull station within 600 mm.
  • In Toronto, a stand-alone mag lock install needs a building permit, at $46.40 per lock up to $463.96 in 2026.
  • The 2024 Ontario Building Code does not allow mag locks on access-to-exit doors in elementary or secondary schools.
  • On a fire-rated door, an electric strike must be a fail-secure model listed for fire doors.

You want a card reader on the server room door, and the installer asks the question every facilities lead hears: mag lock or electric strike? In Toronto, part of the answer sits on the permit page. A mag lock needs a building permit there, and the City lists the fee at $46.40 per lock, up to $463.96, which is usually the smallest line on the job.

For most Ontario server rooms, an electric strike or an electrified lock built into the door is the better fit. The lever inside lets people out without power, and a fail-secure model stays locked when the power drops. A mag lock is allowed on many doors, but only in a building that can meet a list of fire alarm conditions.

Mag lock or electric strike: which fits a server room door?

An electric strike fits most server room doors because it works with a normal latching lockset. It sits in the frame and holds the latch until a valid card releases it. The inside lever opens the door by hand at all times, so leaving the room never depends on power.

A mag lock works the other way, holding the door with an electromagnet. The door unlocks whenever the magnet loses power, and the building code requires it to release on the fire alarm.

Allegion’s codes manager says it plainly in a guide to fail safe and fail secure hardware: “Electromagnetic locks are only available fail safe.” For a room you lock to protect equipment, the door opens in every power cut and every fire alarm.

QuestionElectric strikeElectrified mortise lockMag lock
Power cutStays locked if fail-secureStays locked if fail-secureUnlocks
Leaving the roomInside lever, alwaysInside lever, alwaysNeeds an electric release
Fire alarm tie-inNot usually requiredNot usually requiredRequired by the code
Fire-rated doorFail-secure, listed modelListed modelConfirm with the door’s listing
Extra workFrame prep, compatible locksetWire path through hinge and doorPermit, sealed drawings, verification, signs, lighting

What does the Ontario Building Code require for a mag lock?

The 2024 Ontario Building Code allows a mag lock on an egress door only in a building with a fire alarm system. The lock must also meet every condition in Sentence 3.4.6.16.(5). It has to release on the fire alarm, on power loss, on a wiring fault, from a staff-only switch and from a pull station beside the door, with signs, emergency lighting and a manual reset.

Toronto’s installer’s declaration for electromagnetic locking devices turns that list into a form. It asks for a pull station “within 600mm of the door,” a sign reading EMERGENCY EXIT UNLOCKED BY FIRE ALARM, and emergency lighting. Until the installer and the owner both sign and a verification report is attached, the City says the job “will not be acceptable to Building and Fire Services.”

The City of London’s maglock permit guide, written to the 2024 code, shows the work behind the form. Fire alarm drawings must be “prepared and sealed by a P.Eng. licensed in Ontario.” And the locks “shall be reactivated only by the operation of the authorized manual switch.”

That last rule matters in a server room more than almost anywhere else. After every fire alarm, drill or power cut, the door stays unlocked until an authorized person resets it at the switch.

Can a school, hospital or municipal building use a mag lock on a server room?

Elementary and secondary schools generally cannot. Article 3.3.1.13 of the 2024 code lets a door in an access to exit, which typically includes a server room door, use a mag lock. The permission has a limit, though: it “does not apply to a door (a) in an elementary or secondary school.”

Article 3.4.6.16 adds a similar ban, with narrow exceptions, on exit doors serving those schools. So for a school board, the server room door gets an electric strike or an electrified lock.

Hospitals and care homes need a closer look before you order hardware. The same articles set separate release rules for contained use areas and impeded egress zones.

Universities, municipal offices and bank branches usually fall under the general rule. That brings you back to the first test, because a building without a conforming fire alarm system can’t take a mag lock.

What about an electric strike on a fire-rated server room door?

If your server room door is fire-rated, the strike has to be a fail-secure model listed for fire doors. A rated door must stay latched in a fire, and Allegion’s guide says fail-safe strikes “do not provide the positive latching and the listings required by NFPA 80.” An electrified mortise lock is another option on a rated door, because the latch stays in place and power only controls the outside lever.

Before you order, ask whether the door and frame labels allow the preparation the hardware needs. Cutting a rated frame for a strike, or coring a door for wires, can raise questions at inspection. That is typically where a simple strike turns into a new door.

Who does what, and what drives the cost and schedule?

On a server room door, the security installer usually carries the reader, controller, strike or lock, power supply, door contact, cabling and programming. A mag lock adds an engineer for sealed fire alarm drawings, the fire alarm contractor for release and verification, and the building department for the permit. Each one is another date on your schedule.

TaskStrike or electrified lockMag lock
Reader, controller, lock power, door contact, programmingSecurity installerSecurity installer
Network port and access listYour IT teamYour IT team
Fire alarm release and verificationNot usually neededFire alarm contractor, with the installer
Sealed fire alarm drawingsNot usually neededOntario-licensed P.Eng.
Permit and owner declarationCheck with your building departmentYour facilities lead, with the owner’s signature

Even the signs have rules, and London’s guide asks for visual and tactile signs with characters 16 to 50 mm high. It also asks for at least 10 lux at the door threshold, tied to emergency lighting.

When you compare quotes, look past the price of the lock itself. The total moves with whether the frame takes a strike, whether the door is rated and whether battery backup keeps the reader logging in an outage. For a mag lock, add the drawings, verification, signs and lighting, and our access control page covers the reader side.

How do we bring Securitron in on our server room door?

Book a site walk-through with Securitron. We’ll check the door, frame, fire rating and power at the room, then tell you which lock fits and what approvals it brings. You get a written scope you can use for internal approval or a tender.

If you’re tendering, add Securitron to your invited bidders, and if you can hire directly, we’ll plan the work around your operating hours.

Securitron has installed and serviced access control, cameras, intrusion alarms and structured cabling across the GTA since 2008. In 2026 we installed the security on a newly built Toronto data centre, and our data centre page shows the kind of work involved. Our server room security guide covers the rest of the room, from cameras to the access list.

Frequently Asked Questions

In Toronto, a mag lock installed with no other construction goes through a stand-alone Fire/Security Upgrades building permit, with floor plans showing the maglock and fire alarm layout. If the door is part of a larger renovation, the lock can be included in that renovation's permit instead. Other cities, London among them, publish their own submission guides, so check with your local building department before you order.

A fail-secure electric strike stays locked from the outside when power is cut, and anyone inside can still leave by turning the lever. Put the access control panel and lock power supply on battery backup so the reader and its entry log keep working through short outages, and keep the key cylinder as a manual override.

Often, yes. An electric strike works with the existing latching lockset, so the door can stay and its key remains the override. A new door or frame becomes more likely when the frame can't be prepared, a fire rating limits field work, or you choose an electrified lock that needs wires through the hinge.

Usually not for a server room. A mag lock fails safe, so it unlocks whenever its power is cut or the fire alarm sounds, and under the Ontario Building Code it stays released until an authorized person resets it. A fail-secure strike or electrified lock keeps the room locked through those events while still letting people out.

Securitron installs and services cameras, access control and alarms across the Greater Toronto Area and Hamilton, from our head office in Hamilton. That includes Toronto; Mississauga and Brampton in Peel; Vaughan, Markham and Richmond Hill in York Region; Oakville, Burlington and Milton in Halton; Pickering, Ajax, Whitby and Oshawa in Durham; and Hamilton, Guelph and Kitchener. For a job elsewhere in Ontario, call (905) 730-2425 to check.